đ§ Mounting Geometry
(See plan view below)
Plan view â the "Delta" diagonal path between transducers: Opposite (tunnel width), Adjacent (downstream offset), 30â60° to the flow. Pulses travel both ways along the Delta â the transit-time difference gives speed; its sign gives direction, so flow reversal is detected automatically.Â
Mounting Tip: Â Find a straight tunnel segment at least 3 tunnel-widths long.
Avoid: Corners or areas where airflow hugs the walls; centerline flow should dominate.
Power Requirement: 24VDC @ 200mA (4.8W total system). / 120-220V ACÂ
Default Network Mode: DHCP-enabled â device automatically requests an IP from your router.
type padisco --find
Option C: Configure IP manually:
EDIT microSD card system.jsn file.
Enter static IP settings, save & reboot:
"ipv4": {
  "dhcp": false,
  "ip": "192.168.1.50",
  "mask": "255.255.255.0",
  "gw": "192.168.1.1"
}
No need for manual calibration or baseline input.
True auto-ranging calculates the distance between transducers automatically.
Two signal detectors: choose between high-precision or noise-resistant filtering depending on your environment.
PA Discovery Tool (PADisco)
ModbusScope for Diagnostics
Full SONIC-1 Manual